$120.85$150.99
Prepare to embark on a sensory journey with the Bosco Apple, a fruit that transcends the ordinary and promises an unparalleled taste experience. These apples are nothing short of nature’s masterpiece, celebrated for their distinctive blend of flavors and their captivating visual allure.
Availability: In Stock
The TeSysD TH O/L Relay CL10A 0.63-1.0A is essential for safeguarding electrical motors in various industrial and commercial applications. With a current range of 0.63-1.0A, this relay provides reliable motor protection against overload conditions, ensuring optimal performance and longevity.
This advanced relay is equipped with cutting-edge technology to continuously monitor the current flowing through the motor. In the event of an overload, which could lead to overheating and potential damage, the relay intervenes promptly by disconnecting the engine from the power source. This prevents damage to the motor, minimizes downtime, and avoids costly repairs.
One of the critical features of the TeSysD TH O/L Relay CL10A is its adjustable current range of 0.63-1.0A. This allows users to customize the protection level based on the specific requirements of their motor-driven equipment, providing flexibility in various industrial settings. The relay is designed for easy installation and seamless integration into existing control systems, ensuring a user-friendly and efficient motor protection solution.
| Parameter | Specification |
|---|---|
| Product | Schneider Electric TeSys LRD05 thermal overload relay |
| Series | TeSys / TeSys Deca |
| Relay Type | Differential thermal overload relay |
| Application | Motor protection |
| Adjustable Current Range | 0.63–1 A |
| Tripping Class | Class 10A (IEC 60947-4-1) |
| Rated Insulation Voltage (Ui) | 600 V (CSA/UL), 690 V (IEC) |
| Rated Operational Voltage (Ue) | Up to 690 V AC |
| Frequency | 0–400 Hz |
| Network Type | AC / DC |
| Auxiliary Contacts | 1 NO + 1 NC |
| Thermal Trip Threshold | 1.14 ± 0.06 × Ir |
| Phase Failure Sensitivity | Yes |
| Conventional Free Air Thermal Current (Ith) | 5 A (signalling circuit) |
| Permissible Signalling Current | 3 A @ 120 V AC-15 / 0.22 A @ 125 V DC-13 |
| Impulse Withstand Voltage (Uimp) | 6 kV |
| Connection Type | Screw clamp terminals |
| Reset / Control | Manual or automatic reset, stop & reset buttons |
| Mounting | Directly under contactor, DIN rail, or plate |
| Operating Temperature | –20 °C to +60 °C |
| Storage Temperature | –60 °C to +70 °C |
| Degree of Protection | IP20 |
| Standards / Certifications | IEC, UL, CSA, CCC, EAC, ATEX, Marine, RoHS, REACH |
| Dimensions (H × W × D) | Approx. 66 × 45 × 70 mm |
| Weight | Approx. 0.124 kg |